3-line MRT fault: A timeline of what happened on Oct 14

  • 📰 The Straits Times
  • ⏱ Reading Time:
  • 39 sec. here
  • 2 min. at publisher
  • 📊 Quality Score:
  • News: 19%
  • Publisher: 63%

Singapore Headlines News

Singapore Latest News,Singapore Headlines

The three-hour, 36-minute incident affected 123,000 commuters.. Read more at straitstimes.com.

SINGAPORE - A section of power cable that burnt through and a faulty circuit breaker along the Tuas West Extension were the primary cause of a massive disruption on Oct 14 that affected three MRT lines.

Of these, 6,500 commuters were on 12 stalled trains along the North-South and East-West Lines while 275 were on three stalled Circle Line trains.6.58pm: Concurrent faults along the Tuas West Extension cause a power outage. The burnt section of 22 kilovolt cables between Tuas Link station and Tuas West Road station had triggered a power fault, which activated circuit breakers nearby. But one failed to trip and isolate the power fault as designed due to a melted trip coil.

Train service was shut down between Woodlands and Jurong East stations on the North-South Line and between Queenstown and Gul Circle stations on the East-West Line. Operator SMRT subsequently decided to draw power from the Buona Vista substation, which supplies power to the CCL.

 

Thank you for your comment. Your comment will be published after being reviewed.
Please try again later.
We have summarized this news so that you can read it quickly. If you are interested in the news, you can read the full text here. Read more:

 /  🏆 8. in SG

Singapore Latest News, Singapore Headlines

Similar News:You can also read news stories similar to this one that we have collected from other news sources.

MRT disruption on Oct 14 prompts system overhaul, with early weekend closures from NovemberSINGAPORE: A main contractor of the Land Transport Authority (LTA) will replace 150km of power cables and more than 100 circuit breaker components ... 👍🏽👍🏾👍🏼 for transparency... I think likely due to thermal cycles from our unpredictable weather plus moisture, leading to thermally expanded sagging insulation. Then the faulty insulation touched live high voltage copper resulting in melt down. Insulation does not have consistent thermal expansion.
Source: ChannelNewsAsia - 🏆 6. / 66 Read more »

Two SMRT staff suspended after 'human error' worsened MRT disruption on Oct 14Both SMRT employees had misread equipment at a substation.. Read more at straitstimes.com. WTAF! This is clear scapegoating to save the skins of the top brass where the buck stops. Shameful.
Source: The Straits Times - 🏆 8. / 63 Read more »

All power cables on Tuas West Extension to be replaced following 14 Oct service disruptionFrench firm Alstom will be replacing all power supply cables and breaker trip coils along the Tuas West Extension.
Source: YahooSG - 🏆 3. / 71 Read more »

SMRT: Graphics display misreading contributed to 14 Oct disruption, 2 workers suspendedAn SMRT staff member’s misreading of a graphical display added to the major train service disruption that took place on 14 October. It happened...
Source: YahooSG - 🏆 3. / 71 Read more »

Oct 14 MRT breakdown: Manufacturer to replace power cables along Tuas West Extension, 2 SMRT staff suspendedSINGAPORE — French train manufacturer Alstom will replace 150km of power cables along the Tuas West Extension following a massive train disruption on Oct 14 which affected more than 120,000 passengers and train service on some lines for more than three hours.
Source: TODAYonline - 🏆 1. / 99 Read more »

Timeline: How a power fault caused an hours-long disruption on three MRT lines on Oct 14SINGAPORE: Train services on three MRT lines were disrupted on the evening of Oct 14 due to concurrent electrical faults, affecting 15 trains and ...
Source: ChannelNewsAsia - 🏆 6. / 66 Read more »